Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Building Final
Permit Number - TC-COM-0724-01375
Inspection Description - COT - HCBU - Building Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2025 | COT - HCBU - Building Final | Re-inspection required | 7-29-25: men's restroom flush control valve on water closet must be on accessible side, lower mirror to 40" to reflective surface, missing toilet paper dispenser. Woman's restroom-lower handrails to 36" o.c., missing toilet paper dispenser, lower mirror to 40 " to reflective surface, firefoam penetrations above ceiling tiles directly above electrical panels, insulate hot water line at water heater, missing paper towel dispenser on both restrooms, soap dispenser must be 40" to bottom, female napkin dispenser missing-check ADA requirements., adjust lobby main doors to 5 pounds of pressure. | |
| 08/01/2025 | COT - HCBU - Building Final | Re-inspection required | Per previous notes. 8/1/2025 | |
| 08/06/2025 | COT - HCBU - Building Final | Passed | Approved. 8/6/2025 |