Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Final 

Permit Number - TC-COM-0724-01375

Inspection Description - COT - HCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/29/2025 COT - HCBU - Building Final  Re-inspection required 7-29-25: men's restroom flush control valve on water closet must be on accessible side, lower mirror to 40" to reflective surface, missing toilet paper dispenser. Woman's restroom-lower handrails to 36" o.c., missing toilet paper dispenser, lower mirror to 40 " to reflective surface, firefoam penetrations above ceiling tiles directly above electrical panels, insulate hot water line at water heater, missing paper towel dispenser on both restrooms, soap dispenser must be 40" to bottom, female napkin dispenser missing-check ADA requirements., adjust lobby main doors to 5 pounds of pressure.
08/01/2025 COT - HCBU - Building Final  Re-inspection required Per previous notes. 8/1/2025
08/06/2025 COT - HCBU - Building Final  Passed Approved. 8/6/2025