Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-COM-0626-00867

Parcel: 11706315E


Addresses:

450 S TOOLE AV

Inspection Status: Passed

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
10/15/2026 COT - LCEL - Electrical Underground  Passed 10/15/2026 X2 3” conduit at new meter location. Ran to pole box location. Same x2 3” ran to new disconnect panel location. X4 4” from disconnect to ATS (automatic transfer switch) x4 3” from generator to ATS. X3 1 1/2” for low voltage. From generator to ATS. X1 1” for starter wire. From generator to ATS. X4 3” from transfer switch to new transformer location. X3 4” from new transformer location to directly into panel. X4 4” for alarm wire from gutter box on south end to existing shelter stubbed up on east end. All schedule 40 conduit. Over drive way 48” depth. Conduit east of fencing at 36” depth. Okay to backfill all progress areas. Shading material required. Ensure caution tape is in place after first lift of compaction.