Permit: TC-COM-0625-01114

Parcel: 13219101A


Addresses:

4697 S CAMPBELL AV

Inspection Status: Re-inspection required

Inspection History: COT - HCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
04/01/2026 COT - HCPL - Plumbing Intermediate  Re-inspection required 4-1-26: add supports to DWV at 4' intervals, fire foam all penetrations at top plates and where DWV penetrates exterior walls, add supports to horizontal copper lines at 6' maximum, copper lines 3/4" and larger must be insulated with R3 insulation, add Boca plates to domestic lines and DWV where closer than 1 1/4" from edge of studs.
07/02/2026 COT - HCPL - Plumbing Intermediate  Passed 7-2-26: plumbing intermediates approved.