Permit: TC-COM-0625-01114

Parcel: 13219101A


Addresses:

4697 S CAMPBELL AV

Inspection Status: Partial Pass

Inspection History: COT - HCPL - Yard Water Line 

Date Description Inspector Results Comments
02/05/2026 COT - HCPL - Yard Water Line  Partial Pass Partial pass. water line into building to stubbed up location on test. Okay to backfill progress areas. Shading material is required. Stubbed out of building pending tie into main. 2/5/2026
02/19/2026 COT - HCPL - Yard Water Line  Partial Pass 2-19-26: verified 3' trench depth with a 2" water copper line with tracer wire on an approximate 85' run. Copper line stubs up approximately 12' away from Tucson Water's main line & 2" copper line transitions to 1.5" into building. 2" verified under test at 85psi-okay to backfill progress areas using shading materials.
07/02/2026 COT - HCPL - Yard Water Line  Passed 7-2-26: previously inspected & approved.