Inspection Status: Passed
Inspection History: COT - HCBU - Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 01/10/2025 |
COT - HCBU - Framing |
|
Passed |
|
| 12/24/2024 |
COT - HCBU - Framing |
|
Re-inspection required |
12/24/24: framing at bar section calls for 2x4 at 16"o.c, DWV running through metal studs must be protected with approved method, nail plates required throughout to prevent damage to pex lines in walls, access panels required for A.V.V and water hammer arrestors, receptacles missing per plan throughout, framing not per plan throughout. revision required for changes made for (electrical, framing) |
| 12/27/2024 |
COT - HCBU - Framing |
|
Partial Pass |
Partial pass. Revision has been sent in to match all framing in field. Okay to proceed progress areas at own risk. 12/27/2024 |