Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Passed

Inspection History: COT - HCBU - Framing

Date Description Inspector Results Comments
01/10/2025 COT - HCBU - Framing Passed
12/24/2024 COT - HCBU - Framing Re-inspection required 12/24/24: framing at bar section calls for 2x4 at 16"o.c, DWV running through metal studs must be protected with approved method, nail plates required throughout to prevent damage to pex lines in walls, access panels required for A.V.V and water hammer arrestors, receptacles missing per plan throughout, framing not per plan throughout. revision required for changes made for (electrical, framing)
12/27/2024 COT - HCBU - Framing Partial Pass Partial pass. Revision has been sent in to match all framing in field. Okay to proceed progress areas at own risk. 12/27/2024