Inspection Status: Not Ready

Inspection History: COT - FCON - Fire - Final

Date Description Inspector Results Comments
COT - FCON - Fire - Final Not Ready
COT - FCON - Fire - Final Not Ready Need to have a fire alarm inspection done along with water flow and tamper on the sprinkler system. Need a FACP sign on door leading to the alarm panel, Need a sprinkler knox cap on FDC.