Inspection Status: Passed
Inspection History: COT - HCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 04/25/2025 |
COT - HCEL - Electrical Intermediate |
|
Passed |
|
| 12/24/2024 |
COT - HCEL - Electrical Intermediate |
|
Re-inspection required |
12/24/24: framing at bar section calls for 2x4 at 16"o.c, DWV running through metal studs must be protected with approved method, nail plates required throughout to prevent damage to pex lines in walls, access panels required for A.V.V and water hammer arrestors, receptacles missing per plan throughout, framing not per plan throughout. revision required for changes made for (electrical, framing) |
| 12/27/2024 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
Receptacles that have been removed from the plans have been submitted for revision. Okay to proceed progress areas. 12/27/2024 |