Inspection Status: Passed

Inspection History: COT - HCEL - Electrical Intermediate

Date Description Inspector Results Comments
04/25/2025 COT - HCEL - Electrical Intermediate Passed
12/24/2024 COT - HCEL - Electrical Intermediate Re-inspection required 12/24/24: framing at bar section calls for 2x4 at 16"o.c, DWV running through metal studs must be protected with approved method, nail plates required throughout to prevent damage to pex lines in walls, access panels required for A.V.V and water hammer arrestors, receptacles missing per plan throughout, framing not per plan throughout. revision required for changes made for (electrical, framing)
12/27/2024 COT - HCEL - Electrical Intermediate Partial Pass Receptacles that have been removed from the plans have been submitted for revision. Okay to proceed progress areas. 12/27/2024