Inspection History Details
Inspection Status: Requested
Inspection History: COT - HCPL - Plumbing Intermediate
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - HCPL - Plumbing Intermediate | Requested | |||
| 01/13/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | Level #1 and P-1; waste lines at 2 1/2” - 6” lines under hydro test. | |
| 02/18/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | Level #1; room units and main entry lobby/amenities rooms | |
| 03/17/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 3/17/26: AREA C DWV,PVC,CPVC in rooms (256,257,258,259,260,262) pressure test approved | |
| 03/19/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 3/18/26: Area C (213,215) Area B 255,254,252,253, 212,214,216,218,220,222,224,226,282, 281.1 3/19/26: Area A (228,230,232,234,236,238,240,280.2,280.4,280.1,280.3,280.5,280.6,281,279,278,278.4278.5, 2nd floor elevator lobby,251,250, |
|
| 04/08/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 4/8/26: DWV under test in rooms 362,359,360,358,356 | |
| 04/09/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 4/9/26: 3rd floor Area C pex 362,359,360,358,356, pressure test only | |
| 04/16/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 4/15/26: DWV and Domestic:313,315,357,355,354,352(pex pending),353 |
|
| 04/20/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 4/20/26: Inspection for Plumbing Straps for Level 2213,257,259,260,258,256,254,255,252,253,250,251,279,280.1,280.3,238,236,234,232,230,228,226,224,283,222,220218,216,214,21215, | |
| 04/27/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 4/27/26:Plumbing 316 DWV and pex pressure 322,317,330(PVC),319(pvc),341 (restroom pvc) 441 (restoroom pvc),419,430,417,422, 416,415 restroom only (pvc) | |
| 05/01/2026 | COT - HCPL - Plumbing Intermediate | Re-inspection required | 5.1.26: Hot water lines 3/4" and larger shall be properly insulated with minimum R3 insulation, properly support pex line and DWV throughout, dryer exhaust must be constructed of smooth material, kitchen hood shall be constructed of smooth materials, fire caulking required throughout at common walls, proper secure low voltage, back to back receptacles with inserts are required to have putty pad installed, provide Documentation on how large penetrations will be sealed, separate MC cable from copper lines, seal all penetrations (from low volt, mechanical, sprinkler, plumbing) | |
| 05/04/2026 | COT - HCPL - Plumbing Intermediate | Not Ready | ||
| 05/06/2026 | COT - HCPL - Plumbing Intermediate | Canceled | 5/6/2026 canceled per contractor. | |
| 05/07/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 5/7/2026 Partial pass. DWV and pex under test in all units below. 341,342,343,344,346,348,351,350 441,442,443,444,446,448,451,450. Pending CPVC not under test. Pending 444,344 pex lines. |
|
| 05/15/2026 | COT - HCPL - Plumbing Intermediate | Partial Pass | 4th floor DWV, pex along with CPVC in rooms 413,414,415,457,455,454,452,453 on test. Inter & Above ceiling 3rd floor rooms 362,359,360,358,356,354,352,353,350,351,348,346 approved. Okay to proceed progress areas. 5/15/2026 |
|
| 08/15/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | Waste line at 6” at GL: 2.5/B.5 - E.5. Under hydro test, Ok to cover progress areas at Level P-1. | |
| 08/19/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | Basement level; 4” waste line at D.5/10.5 - 5.5. OK to cover progress areas. | |
| 09/08/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | This inspection is for plumbing underground at GL: 4 - 8/E.9 - F.9. Waste and vent lines at 2” - 6”. Ok to cover progress areas | |
| 09/11/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | Plumbing underground at GL: F.5/9 - 11.5 (3” - 6” waste and vent lines) Ok to cover progress areas. | |
| 09/17/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | Plumbing underground for waste and vents lines (2 1/2” - 6”) at GL: F/7.1 - 12. OK to cover progress areas. | |
| 09/26/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | Plumbing underground: 6” and 4” waste lines at GL: 13/E.5 - A. OK to cover progress areas. | |
| 10/01/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | Plumbing underground for 2” - 4” waste lines at GL: G/7 - 8, 8/G - F. OK to cover progress areas. | |
| 10/02/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | Waste and vent lines at GL: E.9/9 - 10, E.9 - G/9 - 10, (Plumbing underground). Ok to cover progress areas. | |
| 11/20/2025 | COT - HCPL - Plumbing Intermediate | Partial Pass | Waste and vent lines(2 1/2” - 6”) parking garage lower level. All lines are under hydro test. |