Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCBU - TCO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2026 | COT - HCBU - TCO | Partial Pass | 6/3/26: It is acceptable to apply for a Level 3 Temporary Certificate of Occupancy (TCO) for the dealership areas that are currently occupied. Areas that are still under construction shall remain separated from the existing occupied square footage. Please contact the Engineering Final and Plumbing Final inspectors to obtain their recommendations regarding TCO approval. |
|
| 06/29/2026 | COT - HCBU - TCO | Re-inspection required | 6-29-26: missing return/supply at men's restroom,missing men's/woman's restroom signs,adjust restroom doors to 5 pounds of pressure, install soap dispensers. Complete installation of locker equipment at restrooms, Move partition in woman's restroom back to 36" in width, add blank covers to low voltage and complete installation of fire equipment above ceiling, missing light switch covers, and make electrical corrections to power receptacles at restrooms. Obtain clarification on whether restrooms are ment to be ADA, If so, then signs with braille are required, as are knee guards for lavatories p-traps, and mirror above lavatory must be 40" to the reflective surface. | |
| 06/30/2026 | COT - HCBU - TCO | Re-inspection required | 6-30-26: not ready. | |
| 07/02/2026 | COT - HCBU - TCO | Not Ready | Partial pass. Pending sterilization report. 7/2/2026 | |
| 07/07/2026 | COT - HCBU - TCO | Partial Pass | Okay for level 3 TCO at both men's and women's restrooms garage side. Okay to apply for TCO. 7/7/2026 |