Permit: TC-COM-0525-01016

Parcel: 116206340


Addresses:

115 S LINDA AV

Inspection Status: Partial Pass

Inspection History: COT - HCBU - Interior Shear Bracing 

Date Description Inspector Results Comments
04/30/2026 COT - HCBU - Interior Shear Bracing  Partial Pass Verified 2nd and third floor interior hold downs at interior shear walls. 4/30/2026
05/13/2026 COT - HCBU - Interior Shear Bracing  Canceled Canceled per contractor. 5/13/2026
05/18/2026 COT - HCBU - Interior Shear Bracing  Re-inspection required 5/18/26: fasteners at sheathing must be no closer than 3/8" from edge and shall not penetrate more than 1/8", anchor bolts and shot pins must be spaced per approved plans (over spaced throughout), anchor bolts required 12" from edge of sill plate, hold downs verified in correct locations in rooms (123,124,125,126)