Inspection Status: Partial Pass
Inspection History: COT - HCBU - Interior Shear Bracing
| Date |
Description |
Inspector |
Results |
Comments |
| 04/30/2026 |
COT - HCBU - Interior Shear Bracing |
|
Partial Pass |
Verified 2nd and third floor interior hold downs at interior shear walls. 4/30/2026 |
| 05/13/2026 |
COT - HCBU - Interior Shear Bracing |
|
Canceled |
Canceled per contractor. 5/13/2026 |
| 05/18/2026 |
COT - HCBU - Interior Shear Bracing |
|
Re-inspection required |
5/18/26: fasteners at sheathing must be no closer than 3/8" from edge and shall not penetrate more than 1/8", anchor bolts and shot pins must be spaced per approved plans (over spaced throughout), anchor bolts required 12" from edge of sill plate, hold downs verified in correct locations in rooms (123,124,125,126) |