Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-COM-0525-01005

Parcel: 141019160


Addresses:

5651 S HOUGHTON RD

Inspection Status: Partial Pass

Inspection History: COT - HCME - Mechanical Progress 

Date Description Inspector Results Comments
02/11/2026 COT - HCME - Mechanical Progress  Partial Pass Partial pass for poukey on mechanical, ok to proceed
04/10/2026 COT - HCME - Mechanical Progress  Re-inspection required Partial pass for poukey on mechanical, ok to proceed

4/10/26
Flex duct near 1st drive thru window needs to be supported and hooked up to diffuser and insulation on the trunk line behind in support room needs to be fixed and taped. All flex must be supported every 6ft max.
04/17/2026 COT - HCME - Mechanical Progress  Passed