Parcel: 141019160


Addresses:

5651 S HOUGHTON RD


Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Preslab  

Permit Number - TC-COM-0525-01005

Inspection Description - COT - HCBU - Preslab  

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/17/2026 COT - HCBU - Preslab   Re-inspection required 1/16/26: continuous #5 rebar missing at slab per detail S2.3 with additional #4x32" long dowels at 16" o.c at doors, all columns base must be coated with asphaltic paint below grade, holdowns missing at all shear-walls per approved plans, reinforcement not in place around freezer pad per detail S2.7 (missing 2#6 continuous around pad), will need to verify (3) 2x10 redwood sleepers at freezer pad, Recessed slab for mop sinks missing per approved plans at two locations, vapor barrier was never inspected.
COT - HCBU - Preslab   Scheduled