Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Preslab
| Date |
Description |
Inspector |
Results |
Comments |
| 01/17/2026 |
COT - HCBU - Preslab |
|
Re-inspection required |
1/16/26: continuous #5 rebar missing at slab per detail S2.3 with additional #4x32" long dowels at 16" o.c at doors, all columns base must be coated with asphaltic paint below grade, holdowns missing at all shear-walls per approved plans, reinforcement not in place around freezer pad per detail S2.7 (missing 2#6 continuous around pad), will need to verify (3) 2x10 redwood sleepers at freezer pad, Recessed slab for mop sinks missing per approved plans at two locations, vapor barrier was never inspected. |
| 02/06/2026 |
COT - HCBU - Preslab |
|
Passed |
|