Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 01/05/2026 |
COT - LCEL - Electrical Underground |
|
Partial Pass |
1-5-26: verified schedule 40 electrical conduits for panels and stub outs of pad at the east/west sides of site. Conduits range from 3/4" to 2 1/4"- okay to backfill progress areas. |
| 01/13/2026 |
COT - LCEL - Electrical Underground |
|
Passed |
Exterior conduits 1 1/4” and 1 1/2”. Ok to cover progress areas |
| 12/18/2025 |
COT - LCEL - Electrical Underground |
|
Partial Pass |
12-18-25: verified conduit from gear to transformer in electrical room, conduit to exterior transformer, conduit for fiber and conduits to transformer/panels T2 & T3. All conduits are Schedule 40 and range from 1 1/4"-2 1/2"-Okay to backfill progress areas. |