Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Final 

Date Description Inspector Results Comments
01/07/2026 COT - HCBU - Building Final  Re-inspection required 1-7-26: label hydronic piping where change of direction occurs.
01/09/2026 COT - HCBU - Building Final  Passed 1-9-26: building final approved.
12/16/2025 COT - HCBU - Building Final  Partial Pass 12-16-25: adjust restroom doors to 5 pounds of pressure, lower restroom mirrors-40" to the reflective surface, install door leading to break room, install cover plate for low voltage at main entrance floor, install cover plate at west wall upstairs.
Note: submit a 3rd party report for elevator.
12/23/2025 COT - HCBU - Building Final  Re-inspection required 12-23-25: add support to DWV above ceiling at east end of mezzanine, missing plumbing fixture rm. 115, label hydronic piping where change of direction occurs-above ceiling at warehouse, submit elevator certification report, flashing required around exhaust boots on rooftops, adjust restroom doors to 5 pounds of pressure.