Inspection Status: Passed

Inspection History: COT - HCBU - Building Above Ceiling 

Date Description Inspector Results Comments
01/07/2026 COT - HCBU - Building Above Ceiling  Passed 1-7-26: approved.
09/29/2025 COT - HCBU - Building Above Ceiling  Partial Pass 9-29-25: partial pass-see electrical intermediate notes for details
12/16/2025 COT - HCBU - Building Above Ceiling  Partial Pass 12-16-25: partial pass for office areas -1st & 2nd floor. Pending inspection on other half of building.
12/23/2025 COT - HCBU - Building Above Ceiling  Re-inspection required 12-23-25: add support to DWV above ceiling at east end of mezzanine, missing plumbing fixture rm. 115, label hydronic piping where change of direction occurs-above ceiling at warehouse, submit elevator certification report, flashing required around exhaust boots on rooftops, adjust restroom doors to 5 pounds of pressure.