Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical FinalĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 11/04/2026 |
COT - LCEL - Electrical FinalĀ |
|
Re-inspection required |
HVAC #1 calls for 125. 100 amp in place. Future HVAC #5 calls for 70. 100 amp in place. Provide cover plates at open j boxes. Ensure all boxes are labeled. Provide labeling for main distribution panel. Provide full size breaker covers for blanks. Provide torque reports with letter head and upload them to dashboard prior to final. 11/4/2026 |