Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 08/25/2026 |
COT - LCEL - Electrical Underground |
|
Partial Pass |
8-25-26: verified trench depth at 3' on 4-4" & 2-3" schedule 40 conduits together with grounding rods at every 15' cad-welded to copper using a complete grounding ring around shelter building. Conduits & grounding verified per E1.0/Site Electrical & Grounding Plan. Okay to backfill progress areas using shading materials. |