Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 10/09/2025 |
COT - LCEL - Electrical Above Ceiling |
|
Re-inspection required |
10-9-25: block all registers, seal all horizontal/vertical penetrations penetrations, add spacers to mc cables and remove off trusses, add rubber bushings to pex lines and DWV piping running through metal framing. |
| 10/10/2025 |
COT - LCEL - Electrical Above Ceiling |
|
Partial Pass |
10-10-25: in wall electrical for market area not complete, however, in wall/above ceiling at the the market restrooms was verified per plans-okay to,continue construction at hard lid areas. Office space/restrooms electrical approved-okay to continue with TI construction. |
| 12/08/2025 |
COT - LCEL - Electrical Above Ceiling |
|
Partial Pass |
12-8-25: verified electrical conduits for above ceiling lights at mercantile area. I noted that drywall above ceiling in mercantile area was removed and scrim paper was added. Have architect of record submit an updated RFI reflecting changes and include paint requirements for scrim paper using recommended manufactured specifications.Also, document whether the ceiling meets the R-Value & submit an updated electrical plan if you opt to replace exterior lights at awning area. Proceed with construction at mentioned area at own risk. |
| 12/12/2025 |
COT - LCEL - Electrical Above Ceiling |
|
Passed |
12-12-25: approved. |