Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-COM-0524-00998

Parcel: 120077020


Addresses:

4001 S 12TH AV

Inspection Status: Passed

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
01/06/2026 COT - LCEL - Electrical Final  Passed 1/6/2026 all corrections have been made. No additional items.
12/19/2025 COT - LCEL - Electrical Final  Re-inspection required 12-19-25: missing light switch cover in office, label junction boxes and receptacles throughout, install covers on low voltage surface mounted boxes at market areas, label panel at office, seal electrical penetrations at exterior wall of office, install a 50 amp 2-pole breaker for water heater #2, wrap hot leg of water heaters with R3 insulation. Stopped,inspection-additional items may be added.