Inspection Status: Passed
Inspection History: COT - LCEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 01/06/2026 |
COT - LCEL - Electrical Final |
|
Passed |
1/6/2026 all corrections have been made. No additional items. |
| 12/19/2025 |
COT - LCEL - Electrical Final |
|
Re-inspection required |
12-19-25: missing light switch cover in office, label junction boxes and receptacles throughout, install covers on low voltage surface mounted boxes at market areas, label panel at office, seal electrical penetrations at exterior wall of office, install a 50 amp 2-pole breaker for water heater #2, wrap hot leg of water heaters with R3 insulation. Stopped,inspection-additional items may be added. |