Inspection History: COT - HCME - Kitchen Hood
| Date |
Description |
Inspector |
Results |
Comments |
| 01/03/2025 |
COT - HCME - Kitchen Hood |
|
Not Ready |
Gas lines need to be moved away from open cooking flames, below cooking surfaces. |
| 01/13/2025 |
COT - HCME - Kitchen Hood |
|
Passed |
Ansul system has been recharged. |
| 11/05/2024 |
COT - HCME - Kitchen Hood |
|
Not Ready |
Hood needs to be connected to gas service and tested by Fire department. |
| 12/18/2024 |
COT - HCME - Kitchen Hood |
|
Partial Pass |
Grease duct system from kitchen hood to third floor; smoke tested - passed. Remainder of system to be tested later. |
| 12/31/2024 |
COT - HCME - Kitchen Hood |
|
Not Ready |
Contractor cancelled, will reschedule for 2 January. |