Inspection Status: Partial Pass
Inspection History: COT - HCBU - Building Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 09/22/2025 |
COT - HCBU - Building Above Ceiling |
|
Partial Pass |
Revised calculations show one point load, where there are Two, for existing 4 by 8 beam. Plans show beam in center of doorway, when it is actually bearing on wall perpendicular to doorway approximately two feet away from where it is shown. Revise drawings to reflect actual conditions, and submit revision. cover at own risk |