Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Above Ceiling
| Date |
Description |
Inspector |
Results |
Comments |
| 06/09/2026 |
COT - HCEL - Electrical Above Ceiling |
|
Partial Pass |
6-9-26: label all junction boxes above ceiling, open knockout at j-boxes at entryway, add independent supports to rigid conduit at same location (cannot rest on grid). |