Inspection Status: Re-inspection required
Inspection History: COT - LCBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 01/23/2026 |
COT - LCBU - Building Final |
|
Re-inspection required |
1-23-26: replace damaged exterior receptacle cover to a bubble cover type that is rated "heavy duty" and gfci to a weather resistant receptacle. Additionally, plans called for weatherproof covers at multi meter pack with (2)125/2 breakers for indicated units to be replaced. The covers were replaced but the breakers are not legible & I could not verify service. Replace breakers, make other corrections and reschedule an inspection. |
| 01/29/2026 |
COT - LCBU - Building Final |
|
Passed |
1-29-26: electrical, mechanical, mechanical intermediate and building final approved. |