Permit: TC-COM-0424-00665

Parcel: 13801001D


Addresses:

6100 S 12TH AV

Inspection Status: Re-inspection required

Inspection History: COT - LCPL - Yard Water Line 

Date Description Inspector Results Comments
01/16/2026 COT - LCPL - Yard Water Line  Re-inspection required 1-16-26: plans call for a 6" main water, missing tracer wire, and Fire Marshall must inspect fire water line.
01/21/2026 COT - LCPL - Yard Water Line  Partial Pass 1-21-26: verified trench depth at 4' for a 3" main pvc water line. A revision showing 6" to 3" has been submitted to the city for review. Okay to backfill approximately 300' of open trench with shading materials at own risk pending revision city approval. Water pressure test will be conducted at a later date.
02/02/2026 COT - LCPL - Yard Water Line  Partial Pass 2-2-26: approximately 200' of 3" water line. Contact Tucson Water and seek clarification whether they need to be involved with observing installation of water lines. In addition Tucson Fire inspecting fire line, it is understanding that Tucson Water must also inspect it. Okay to backfill using shading materials at own risk.
02/06/2026 COT - LCPL - Yard Water Line  Partial Pass 2-6-26: okay to backfill approximately 120' of open trench using shading materials on a 3 water line.
02/18/2026 COT - LCPL - Yard Water Line  Partial Pass 2-18-26: water main line test at 62psi. Verified that line was under pressure for more than 15 minutes. Total length of run is a total of 980' -okay to continue with project at progress areas. Note: pending city approval from city on RFI from 6" to 3" water line.
07/08/2026 COT - LCPL - Yard Water Line  Passed