Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Pass
Inspection History: BULD - Electrical Clearance
Permit Number - TC-COM-0423-01135
Inspection Description - BULD - Electrical Clearance
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2024 | BULD - Electrical Clearance | Partial Pass | clearance for house panel only | |
| 04/22/2024 | BULD - Electrical Clearance | Not Ready | ||
| BULD - Electrical Clearance | Passed | Please supply letter of torque several connections do not have corrosion prevention compound and all connections need to be torqued striped 4/24/24: Letter of Torque provided at time of inspection. Corrosion prevention compound added to all feeders, ECO TEP CLEARANCE for meter 3476 S KINO PW and OWNER meter |
||
| 04/30/2024 | BULD - Electrical Clearance | Passed | 4/30/24: ECO for OWNER meter at 3476 S KINO PW. | |
| 12/13/2023 | BULD - Electrical Clearance | Passed |