Inspection Status: Re-inspection required
Inspection History: COT - HCPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 05/19/2025 |
COT - HCPL - Plumbing Final |
|
Re-inspection required |
5-19-25, seal base of water closet, flush control must be on accessible side, missing knee guards, missing men/woman's sign with braile, missing 90 degree elbow on PTR line/and condensation line,paint all exterior plastics, missing knockout at panel, secure a/c whip, condenser over amped-15 maximum, cut cleanouts to grade and paint/coat to protect from elements. |
| 05/27/2025 |
COT - HCPL - Plumbing Final |
|
Passed |
5-27-25, all corrections made. Plumbing & mechanical final approved. |