Permit: TC-COM-0326-00366

Parcel: 12904251A


Addresses:

331 S OLSEN AV

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Intermediate

Date Description Inspector Results Comments
08/28/2026 COT - LCEL - Electrical Intermediate Re-inspection required 8-28-26: only in wall electrical intermediates at wood framing areas inspected. Fire foam all penetrations at top plates & complete all other in wall electrical at masonry areas. Several receptacles were removed throughout while others were added, therefore, an updated electrical RFI with load calculations is required. Submit the RFI to the city for review/approval.