Inspection Status: Re-inspection required

Inspection History: COT - HCME - Mechanical Above Ceiling

Date Description Inspector Results Comments
08/13/2026 COT - HCME - Mechanical Above Ceiling Re-inspection required 8-13-26: open office space/106, 207,108, , 111-provide supports where flex is not on ceiling grid, 110-provide supports, add supports to flex within 2' of a bend and 4' thereafter, 107, 112-add support at elbow, 112-tear on flex & supports at 4', 103, 101, 104-flex off grid, 116-supports to flex where resting on grid, 115 & 114. Make corrections and reschedule an inspection.
08/18/2026 COT - HCME - Mechanical Above Ceiling Partial Pass 8-18-26: corrections to above ceiling mechanical from inspection dated 8/13/26 made. Okay to continue with construction at progress areas.
08/21/2026 COT - HCME - Mechanical Above Ceiling Passed