Inspection Status: Re-inspection required

Inspection History: COT - HCEL - Electrical Above Ceiling 

Date Description Inspector Results Comments
06/30/2026 COT - HCEL - Electrical Above Ceiling  Re-inspection required 6-30-26: per NEC 300.11, MC Cabling must be independently supported from from the t-grid/ceiling grid. Remove Mc cables from grid at all restrooms & add knockouts for 2 above ceiling junction boxes.
08/07/2026 COT - HCEL - Electrical Above Ceiling  Passed 8-7-26: electrical above ceiling approved.