Permit: TC-COM-0326-00334

Parcel: 11805002A


Addresses:

1665 S LA CHOLLA BL

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
09/25/2026 COT - LCEL - Electrical Final  Re-inspection required 9/25/26: receptacles at new pump room shall gfci weather resistant receptacles, plans call for a 20amp breaker at panel PHP heat pump currently has a 15amp breaker, provide an updated panel schedule.
10/19/2026 COT - LCEL - Electrical Final  Partial Pass Partial pass, corrections made, new splash pad panel not per approved plans, needs revision as on site electrician states wiring per plan would be unsafe and that pups listed for 20 amp breaker are actually low voltage
10/21/2026 COT - LCEL - Electrical Final  Passed 10/21/26: electrical final approved.