Permit: TC-COM-0325-00586

Parcel: 110083060


Addresses:

2475 N SWAN RD

Inspection Status: Not Ready

Inspection History: COT - FCON - Fire - Final

Date Description Inspector Results Comments
COT - FCON - Fire - Final Not Ready
COT - FCON - Fire - Final Not Ready Alarm notification is required throughout building due to its A-3 occupancy and occupant load of 450 people.
COT - FCON - Fire - Final Not Ready Need correct labeled keys for Knoxbox.
06/12/2026 COT - FCON - Fire - Final Partial Pass Exposed wires in the IT room shall be removed, Old fire alarm panel shall be removed, EM lights shall be repaired, Places of assembly permit shall be applied for, Knox box, sprinkler trims shall be installed.
06/16/2026 COT - FCON - Fire - Final Partial Pass Ok for Level 4 TCO. Waiting on Knox box to get installed.
06/26/2026 COT - FCON - Fire - Final Passed