Inspection Status: Canceled

Inspection History: COT - HCBU - Building Final 

Date Description Inspector Results Comments
01/05/2026 COT - HCBU - Building Final  Canceled 1-5-26: canceled by contractor.
01/14/2026 COT - HCBU - Building Final  Re-inspection required 1-12-26: lower warehouse bathroom mirror to 40" to the reflective surface, adjust restroom door to 5pounds of pressure, adjust door pressure to 5 pounds at warehouse to office, provide supports for condensation line above restroom at warehouse,unable to test hot water due to chlorination test.
01/20/2026 COT - HCBU - Building Final  Passed 1-20-26: building final approved.