Inspection Status: Re-inspection required
Inspection History: COT - HCPL - Plumbing Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2026 |
COT - HCPL - Plumbing Intermediate |
|
Re-inspection required |
6-25-26: add strap to in wall DWV, install a Boca plate at sill where DWV is closer than 1 1/4" from edge, place DWV and in wall domestic under test. |
| 06/26/2026 |
COT - HCPL - Plumbing Intermediate |
|
Partial Pass |
6-26-26: plumbing intermediate's & plumbing above ceiling inspection-corrections made at corridor, men's/woman's restroom, and janitor's room. DWV & domestic verified under test. Okay to continue with construction at progress areas. |