Inspection Status: Re-inspection required
Inspection History: COT - LCBU - Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2025 | COT - LCBU - Framing | Re-inspection required | 1-Complete MEP rough-in. 2-Complete porch. 3-Provide truss drawings. 4- Openings larger than 5' require double king studs. 5-Provide detail of framing at hall opening, where bearing masonry wall is being removed. Note connection details for existing roof structure. 6-Add foundation bolt in plate at North end of double door. 7 -Add powder actuated pins where missing. 8- Double door header is a double and should be a triple. |
|
| 12/09/2025 | COT - LCBU - Framing | Passed | Passed 12/9/25 |