Permit: TC-COM-0323-00934

Parcel: 11504480A


Addresses:

1020 N TYNDALL AV

Inspection Status: Not Ready

Inspection History: COT - FCON - Alarm - Final

Date Description Inspector Results Comments
COT - FCON - Alarm - Final Not Ready Fire alarm coverage for the newly enclosed area needs to be evaluated by licensed contractor.
02/15/2024 COT - FCON - Alarm - Final Passed
01/04/2024 COT - FCON - Alarm - Final Re-inspection required Smoke detectors in new gym need to be re-installed and the fire alarm needs to be fully operational.
02/07/2024 COT - FCON - Alarm - Final Re-inspection required Smoke detectors have tape covering them up, the tape shall be removed and a report from the alarm contractor showing the detectors are reporting to the panel.