Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - LCBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2024 | COT - LCBU - Building Final | Re-inspection required | 7/16/24: please upload Air balance report to portal for approval, ADA requirements not met at restrooms, evap cooler not properly installed missing 1/2" cold water supply and 3/4" drain, grease box and pipe missing at kitchen exhaust fan, make up air clearance from exhaust not met. sediment traps required at HVAC units, Properly insulate/Coat refrigerant lines on roof, receptacle missing at makeup air for pump, entry door must be replaced, drive-thru not complete. | |
| 07/30/2024 | COT - LCBU - Building Final | Passed | 7/16/24: please upload Air balance report to portal for approval, ADA requirements not met at restrooms, evap cooler not properly installed missing 1/2" cold water supply and 3/4" drain, grease box and pipe missing at kitchen exhaust fan, make up air clearance from exhaust not met. sediment traps required at HVAC units, Properly insulate/Coat refrigerant lines on roof, receptacle missing at makeup air for pump, entry door must be replaced, drive-thru not complete. 7/30/24: ok for CofO |