Inspection Status: Re-inspection required

Inspection History: COT - LCBU - Building Final 

Permit Number - TC-COM-0323-00866

Inspection Description - COT - LCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/16/2024 COT - LCBU - Building Final  Re-inspection required 7/16/24: please upload Air balance report to portal for approval, ADA requirements not met at restrooms, evap cooler not properly installed missing 1/2" cold water supply and 3/4" drain, grease box and pipe missing at kitchen exhaust fan, make up air clearance from exhaust not met. sediment traps required at HVAC units, Properly insulate/Coat refrigerant lines on roof, receptacle missing at makeup air for pump, entry door must be replaced, drive-thru not complete.
07/30/2024 COT - LCBU - Building Final  Passed 7/16/24: please upload Air balance report to portal for approval, ADA requirements not met at restrooms, evap cooler not properly installed missing 1/2" cold water supply and 3/4" drain, grease box and pipe missing at kitchen exhaust fan, make up air clearance from exhaust not met. sediment traps required at HVAC units, Properly insulate/Coat refrigerant lines on roof, receptacle missing at makeup air for pump, entry door must be replaced, drive-thru not complete.
7/30/24: ok for CofO