Inspection Status: Re-inspection required
Inspection History: COT - LCBU - Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2026 |
COT - LCBU - Framing |
|
Re-inspection required |
7-31-26: expansion bolts and washers are required at pony walls-see A8/Detail 7A, add shot pins at interior partition walls 32" o.c. And 6" within the ends of each plate, add backing to restrooms. |
| 08/26/2026 |
COT - LCBU - Framing |
|
Passed |
8-26-26: framing approved. Okay to continue with construction at progress areas. |
| 08/26/2026 |
COT - LCBU - Framing |
|
Passed |
8-26-26: framing approved. Okay to continue with construction at progress areas. |