Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - LCEL - Electrical Above Ceiling
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2026 | COT - LCEL - Electrical Above Ceiling | Partial Pass | 4-24-26: partial pass at electrical above ceiling. Okay to continue with construction at progress areas. | |
| 04/29/2026 | COT - LCEL - Electrical Above Ceiling | Partial Pass | 4-29-26: have engineer/architect submit the RFI showing elimination of Panel D. Provide updated electrical panel schedules together with load calculations. No more than 3 Mc cables are allowed to be zip-tied together, however, they must be listed & identified for securement and support per NEC 330.30A. Note: at finals-we will be verifying that all junction boxes above ceiling & disconnects are labeled. |
|
| 05/04/2026 | COT - LCEL - Electrical Above Ceiling | Passed | 5-4-26: approved. |