Permit: TC-COM-0226-00148

Parcel: 137279880


Addresses:

1530 W VALENCIA RD

Inspection Status: Partial Pass

Inspection History: COT - LCEL - Electrical Above Ceiling 

Date Description Inspector Results Comments
04/24/2026 COT - LCEL - Electrical Above Ceiling  Partial Pass 4-24-26: partial pass at electrical above ceiling. Okay to continue with construction at progress areas.
04/29/2026 COT - LCEL - Electrical Above Ceiling  Partial Pass 4-29-26: have engineer/architect submit the RFI showing elimination of Panel D. Provide updated electrical panel schedules together with load calculations. No more than 3 Mc cables are allowed to be zip-tied together, however, they must be listed & identified for securement and support per NEC 330.30A.
Note: at finals-we will be verifying that all junction boxes above ceiling & disconnects are labeled.
05/04/2026 COT - LCEL - Electrical Above Ceiling  Passed 5-4-26: approved.