Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-COM-0226-00148

Parcel: 137279880


Addresses:

1530 W VALENCIA RD

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
05/04/2026 COT - LCEL - Electrical Final  Re-inspection required 5-4-26: label junction box above ceiling near soda machine, adjust woman's restroom door to 5 pounds of pressure, all kitchen receptacles must be gfci, add R3 insulation to hot side of water heater, label subpanels ( revision required on electrical-see previous notes)open knockout at middle subpanel, plumbing " as built" revision on floor sinks required, complete installation of grease box-see sheet 8 for details, install condenser on rooftop and complete installation of pending equipment, paint all plastic at rooftop, label disconnect to at rooftop, replace rooftop receptacle to a "weather resistant " gfci and install a bubble cover, add supports to flex at 4' intervals-cannot rest on ceiling grid. This also applies to electrical & plumbing. Install cover plate at exposed electrical box at drive-thru and seal any penetrations at drive-thru. Install See- pending conditions and submit all 3rd party reports to the city for review.Stopped inspection-additional items may be noted.
05/06/2026 COT - LCEL - Electrical Final  Partial Pass 5-6-26: pending kitchen hood inspection & existing conditions, pending plumbing "as built" letter from architect regarding use of existing floor drains and an RFI for electrical schedule & elimination of an existing panel.
Note: once electrical RFI is reviewed & approved, we will re-inspect panels.