Parcel: 13805045F


Addresses:

660 W VALENCIA RD


Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Final 

Permit Number - TC-COM-0225-00336

Inspection Description - COT - LCEL - Electrical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
COT - LCEL - Electrical Final  Re-inspection required 8-6-25: missing label on subpanel, number subpanel to match schedule, missing address identification on front of building, adjust restroom & main entrance door to 5 pounds of pressure, toilet paper holder must be located 3' from wall.
08/08/2025 COT - LCEL - Electrical Final  Passed 8-8-25: electrical final approved.