Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Final
Permit Number - TC-COM-0224-00311
Inspection Description - COT - LCEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2026 | COT - LCEL - Electrical Final | Re-inspection required | 1-9-26: label water heater disconnect, missing light switch cover in restroom, lights not working on restroom, missing junction box lid at warehouse area, cover exposed electrical wiring above ceiling at front lobby, install a clamp for metallic conduit above ceiling for the heater located southwest area of warehouse, label panel "HW" and provide panel schedules for each, label surveillance junction boxes, complete installing disconnect whips at rooftop, properly secure disconnect mounting brackets at rooftop. | |
| 01/21/2026 | COT - LCEL - Electrical Final | Passed | 1-21-26: electrical final approved. |