Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 01/19/2024 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
|
| 01/22/2024 |
COT - HCEL - Electrical Intermediate |
|
Passed |
|
| 12/12/2023 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
12/12/23: 30' of 4" PVC underground conduit per plan form building to property fence pending 15' run to transformer. Ok to backfill progress area. 120' of 4" PVC underground conduit from property fence on southwest end to proposed new building on neighboring lot (pending revised plans to add new structure) ok to back fill progress area. |