Inspection Status: Canceled
Inspection History: COT - LCEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2026 | COT - LCEL - Electrical Final | Canceled | ||
| 06/01/2026 | COT - LCEL - Electrical Final | Re-inspection required | 6/1/26 1. Loose receptacles throughout 2. Each exam room is calling for dedicated breaker for the receptacles 3. Receptacles within 60"of sink needs to be GFCI protected 4. Receptacles in common areas need to be tamper resistant. |
|
| 06/05/2026 | COT - LCEL - Electrical Final | Passed | Passed |