Permit: TC-COM-0125-00139

Parcel: 141186530


Addresses:

10096 E OLD VAIL RD

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Grounding/BondingĀ 

Date Description Inspector Results Comments
03/13/2026 COT - LCEL - Grounding/BondingĀ  Re-inspection required 3/13/26: electrical underground for 4 light poles approved (1" conduit per approved plans ok to proceed with backfill) shading required, missing 4" conduit for telephone per approved plans currently installed a 2", ground not per approved plans must be cadweld or thermoweld exothermic ( ground rods must be driven flush with earth), meter enclosure required for clearance and address tag also required, torque report required, conduit must be per approved plans for underground from transformer to CT cabinet, pull string required and conduit run must be completed.