Inspection History: COT - LCEL - Outdoor Lighting

Permit Number - TC-COM-0125-00139

Inspection Description - COT - LCEL - Outdoor Lighting

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/13/2026 COT - LCEL - Outdoor Lighting Re-inspection required 3/13/26: electrical underground for 4 light poles approved (1" conduit per approved plans ok to proceed with backfill) shading required, missing 4" conduit for telephone per approved plans currently installed a 2", ground not per approved plans must be cadweld or thermoweld exothermic ( ground rods must be driven flush with earth), meter enclosure required for clearance and address tag also required, torque report required, conduit must be per approved plans for underground from transformer to CT cabinet, pull string required and conduit run must be completed.