Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Underground
Permit Number - TC-COM-0125-00139
Inspection Description - COT - LCEL - Electrical Underground
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2026 | COT - LCEL - Electrical Underground | Re-inspection required | 3/13/26: electrical underground for 4 light poles approved (1" conduit per approved plans ok to proceed with backfill) shading required, missing 4" conduit for telephone per approved plans currently installed a 2", ground not per approved plans must be cadweld or thermoweld exothermic ( ground rods must be driven flush with earth), meter enclosure required for clearance and address tag also required, torque report required, conduit must be per approved plans for underground from transformer to CT cabinet, pull string required and conduit run must be completed. | |
| 08/28/2025 | COT - LCEL - Electrical Underground | Partial Pass | 8-28-25: verified 1-1" Schedule 40 conduit with 1/0 copper attached to reinforcement. Okay to pour. |