Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Final
Permit Number - TC-COM-0125-00107
Inspection Description - COT - HCEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2026 | COT - HCEL - Electrical Final | Re-inspection required | 1/22/25: revision for changes to restrooms must be submitted and approved prior to approval. Water sterilization report required, Mirror in restrooms must be no higher than 40" to reflective surface, plumbing incomplete in mechanical room, exterior receptacles shall have appropriate covers at time of final inspection, all cover plates used on exterior of building must be weather rated, emergency lighting not per approved plans missing exit signs throughout (revision submitted 1/22/26 show same set up as original plan), carbon monoxide detector required in mechanical room, hardware at egress doors is none compliant keyed lock are not allowed per IBC 1010.1.9, site work is still in progress and accessible route is currently non compliant. INSPECTION STOPPED. | |
| 01/26/2026 | COT - HCEL - Electrical Final | Passed |