Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-COM-0124-00199

Parcel: 129091410

Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Intermediate

Date Description Inspector Results Comments
07/14/2026 COT - HCEL - Electrical Intermediate Partial Pass 7-14-26: partial pass for phase 1 dock loading/warehouse electrical intermediate. Label all junction boxes and disconnects, verify that 3/4" rigid electrical conduit is supported at 10' maximum intervals and 12' for 1" conduit.