Inspection Status: Partial Pass
Inspection History: COT - HCEL - Electrical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 07/14/2026 |
COT - HCEL - Electrical Intermediate |
|
Partial Pass |
7-14-26: partial pass for phase 1 dock loading/warehouse electrical intermediate. Label all junction boxes and disconnects, verify that 3/4" rigid electrical conduit is supported at 10' maximum intervals and 12' for 1" conduit. |