Inspection Status: Correction Required
Inspection History: MOBILE HOME ELECTRICAL
Permit Number - T99MH00608
Inspection Description - MOBILE HOME ELECTRICAL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2000 | MOBILE HOME ELECTRICAL | Correction Required | ADDTL COMMS - 1. IDENTIFY GROUND WIRE GREEN AND A PERMIT AND INSPECTION REQUIRED FOR NEW PEDESTAL WILL NEED REVISED C-11 CONTRATOR FOR OTHER PERMIT. | |
01/12/2000 | MOBILE HOME ELECTRICAL | Partial Approval | IVRS - Inspection 0000* | |
12/17/1999 | MOBILE HOME ELECTRICAL | Correction Required | ADDTL COMMS - 1. PROVIDE COMPRESSION CONNECTORS ON E.M.T. CONDUIT INTO PEDESTAL. 2. PVC CONDUIT IS NOT MARKED SCHD.80 OR AS APPROVED FOR EXTERIOR. (EXTRA HEAVY DUTY) MAIN LINES INTO PEDESTAL. 3. TAPE NEUTRAL COND. AT PEDESTAL AND AT INTERIOR MAIN PANEL WITH WHITE TAPE AND VERIFY ITIS THE SAME CONDUCTOR. 4. EXPOSE THE GROUND RODS AND THE GROUNDING ELECTRODE CONDUCTOR. | |
12/17/1999 | MOBILE HOME ELECTRICAL | Denied | IVRS - Inspection 0215* |