Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/29/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. I.D. NEUTRAL WHITE 2. PLASTIC ADDRESS NOT ACCEPTABLE PER T.E.P. (USE METAL TAG OR OTHER UTILITY APPROVED METHOD) 3. NEED NAME OR ELEC, CONTRACTOR DOING THIS JOB LEAVE NAME AND LIC# AT 791-5550 X136 4. SERVICE MOUNTED TOO HIGH METER BASE IS NOT TO EXCEED 63 TO CENTER ALSO MAIN BREAKER CANT BE HIGHER THAN 6 OER B.E.C. 380-8 5. INSTALL #4 WATER BOND FOR 200 AMP SERVICE |
| 12/29/1999 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |